450/750V & 600/1000V Single Core XLPE Insulated Unsheathed fire resistant cable to IEC 331& BS 6387
Construction
Conductor: Plain annealed
Fire barrier : Mica Tape
Insulation: XLPE
MODEL |
(450/750V) |
(600/1000V) |
Conductor |
Nom. Thickness
of Insulation
|
Approx. Overall Diameter |
Approx. Weight |
Nominal Thickness of Insulation |
Approx
Overall Diameter
|
Approx. Weight |
Size |
No/Dia. of Wire |
Approx. Diameter. |
mm2 |
No/mm |
mm |
mm |
mm |
kg/km |
mm |
mm |
kg/km |
1.5 |
7/0.53CR |
1.59 |
0.7 |
3.6 |
28 |
0.8 |
3.8 |
30 |
2.5 |
7/0.67CR |
2.01 |
0.8 |
4.2 |
40 |
0.8 |
4.2 |
40 |
4 |
7/0.85CR |
2.55 |
0.8 |
5.0 |
58 |
1.0 |
5.3 |
65 |
6 |
7/1.04CR |
3.12 |
0.8 |
5.5 |
80 |
1.0 |
6.0 |
85 |
10 |
7/1.35CR |
4.05 |
1.0 |
7.0 |
130 |
1.0 |
7.0 |
130 |
16 |
7/1.70CR |
5.10 |
1.0 |
8.0 |
190 |
1.0 |
8.0 |
190 |
25 |
7/2.14CP |
6.10 |
1.2 |
9.5 |
285 |
1.2 |
9.5 |
285 |
35 |
7/2.52CP |
7.10 |
1.2 |
10.5 |
380 |
1.2 |
10.5 |
380 |
50 |
19/1.78CP |
8.40 |
1.4 |
12.0 |
510 |
1.4 |
12.0 |
510 |
70 |
19/2.14CP |
9.90 |
1.4 |
13.5 |
715 |
1.4 |
13.5 |
715 |
95 |
19/2.52CP |
11.8 |
1.6 |
16.0 |
980 |
1.6 |
16.0 |
980 |
120 |
37/2.03CP |
13.2 |
1.6 |
17.5 |
1220 |
1.6 |
17.5 |
1220 |
150 |
37/2.25CP |
14.8 |
1.8 |
19.5 |
1500 |
1.8 |
19.5 |
1500 |
185 |
37/2.52CP |
16.4 |
2.0 |
21.5 |
1870 |
2.0 |
21.5 |
1870 |
240 |
37/2.88CP |
19.0 |
2.2 |
24.5 |
2445 |
2.2 |
24.5 |
2445 |
300 |
61/2.52CP |
21.2 |
2.4 |
27.0 |
3050 |
2.4 |
27.0 |
3050 |
400 |
61/2.85CP |
23.7 |
2.6 |
30.0 |
3880 |
2.6 |
30.0 |
3880 |
500 |
61/3.20CP |
27.0 |
2.8 |
33.5 |
4950 |
2.8 |
33.5 |
4950 |
630 |
91/2.97CP |
31.2 |
2.8 |
38.0 |
6325 |
2.8 |
38.0 |
6325 |
|
Note: |
CR = Circular stranded conductor |
CP = Circular compacted stranded conductor |
website: www.caledonian-cables.com
email: sales@caledonian-cables.com